PT-2011-4389 · Siemens · Siemens Wincc Runtime Advanced Loader+2

Publicado

2011-09-15

·

Atualizado

2017-08-29

·

CVE-2011-3321

CVSS v2.0

9.3

Alta

VetorAV:N/AC:M/Au:N/C:C/I:C/A:C
Name of the Vulnerable Software and Affected Versions Siemens WinCC Runtime Advanced Loader (affected versions not specified) SIMATIC WinCC flexible Runtime (affected versions not specified) SIMATIC WinCC (TIA Portal) Runtime Advanced (affected versions not specified)
Description The issue is related to a heap-based buffer overflow that can be triggered by sending a crafted packet to TCP port 2308. This can lead to memory corruption, causing a denial of service, or potentially allow the execution of arbitrary code.
Recommendations For Siemens WinCC Runtime Advanced Loader, restrict access to TCP port 2308 until a fix is available. For SIMATIC WinCC flexible Runtime, consider implementing network segmentation to limit the exposure of the vulnerable service. For SIMATIC WinCC (TIA Portal) Runtime Advanced, as a temporary workaround, consider disabling the service that listens on TCP port 2308 until a patch is available. At the moment, there is no information about a newer version that contains a fix for this vulnerability.

Buffer Overflow

Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾

Enumeração de Fraquezas

Identificadores relacionados

CVE-2011-3321

Produtos afetados

Simatic Wincc (Tia Portal) Runtime Advanced
Simatic Wincc Flexible Runtime
Siemens Wincc Runtime Advanced Loader