PT-2012-5554 · Rockwell Automation Allen Bradley · Plc-5+2
Publicado
2012-12-08
·
Atualizado
2013-05-21
·
CVE-2012-4690
CVSS v2.0
7.1
Alta
| Vetor | AV:N/AC:M/Au:N/C:N/I:N/A:C |
Name of the Vulnerable Software and Affected Versions
Rockwell Automation Allen-Bradley MicroLogix controller versions 1100, 1200, 1400, and 1500
SLC 500 controller platform
PLC-5 controller platform
Description
The issue allows remote attackers to cause a denial of service via messages that trigger modification of status bits when Static status is not enabled.
Recommendations
For Rockwell Automation Allen-Bradley MicroLogix controller versions 1100, 1200, 1400, and 1500, enable Static status to prevent modification of status bits.
For SLC 500 controller platform, enable Static status to prevent modification of status bits.
For PLC-5 controller platform, enable Static status to prevent modification of status bits.
Correção
DoS
Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾
Enumeração de Fraquezas
Identificadores relacionados
Produtos afetados
Micrologix
Plc-5
Sl 500