PT-2014-2002 · Softing · Softing Fg-100 Pb Profibus

Publicado

2014-09-15

·

Atualizado

2018-10-09

·

CVE-2014-6617

CVSS v2.0

10

Alta

VetorAV:N/AC:L/Au:N/C:C/I:C/A:C
Name of the Vulnerable Software and Affected Versions Softing FG-100 PB PROFIBUS firmware version FG-x00-PB V2.02.0.00
Description The issue is related to a hardcoded password for the root account in the firmware, allowing remote attackers to gain administrative access via a TELNET session. This is due to the use of predefined credentials. An attacker can exploit this to obtain root access to the device using a Telnet connection.
Recommendations For Softing FG-100 PB PROFIBUS firmware version FG-x00-PB V2.02.0.00, consider changing the hardcoded password for the root account to a unique and secure password to prevent unauthorized access. As a temporary workaround, consider disabling TELNET access until a patch is available. Restrict access to the device to minimize the risk of exploitation.

Exploit

Correção

Using Hardcoded Credentials

Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾

Enumeração de Fraquezas

Identificadores relacionados

BDU:2018-00700
CVE-2014-6617

Produtos afetados

Softing Fg-100 Pb Profibus