PT-2017-3322 · Belden · Belden Hirschmann Tofino Xenon Security Appliance

Julien Lenoir

·

Publicado

2017-11-06

·

Atualizado

2019-10-03

·

CVE-2017-11402

CVSS v3.1

10

Crítica

VetorAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Name of the Vulnerable Software and Affected Versions Belden Hirschmann Tofino Xenon Security Appliance versions prior to 03.2.00
Description The issue is related to design flaws in OPC classic and custom netfilter modules, allowing an attacker to remotely activate rules on the firewall and connect to any TCP port of a protected asset, thus bypassing the firewall. The attack methodology involves a crafted OPC dynamic port shift. This is due to errors in security settings of the OPC Classic protocol implementation.
Recommendations For versions prior to 03.2.00, update to version 03.2.00 or later to resolve the issue. As a temporary workaround, consider restricting access to the OPC classic protocol and custom netfilter modules to minimize the risk of exploitation.

Correção

RCE

Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾

Enumeração de Fraquezas

Identificadores relacionados

BDU:2018-00087
CVE-2017-11402

Produtos afetados

Belden Hirschmann Tofino Xenon Security Appliance