PT-2019-15352 · Siemens · Sppa-T3000 Application Server
Publicado
2019-12-12
·
Atualizado
2022-03-04
·
CVE-2019-18332
CVSS v3.1
5.3
Média
| Vetor | AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N |
Name of the Vulnerable Software and Affected Versions
SPPA-T3000 Application Server versions prior to Service Pack R8.2 SP2
Description
A vulnerability has been identified that allows an attacker with network access to gain access to directory listings of the server by sending specifically crafted packets to "80/tcp", "8095/tcp", or "8080/tcp". The attacker must have network access to the Application Server to exploit this issue. At the time of advisory publication, no public exploitation of this security issue was known.
Recommendations
For versions prior to Service Pack R8.2 SP2, update to Service Pack R8.2 SP2 or later to resolve the issue. As a temporary workaround, consider restricting access to the affected ports "80/tcp", "8095/tcp", and "8080/tcp" to minimize the risk of exploitation.
Correção
Improper Authentication
Information Disclosure
Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾
Identificadores relacionados
Produtos afetados
Sppa-T3000 Application Server