PT-2012-5353 · Sielco Sistemi · Winlog Pro Scada+1
Luigi Auriemma
·
Published
2012-08-19
·
Updated
2012-08-20
·
CVE-2012-4356
CVSS v2.0
4.3
Medium
| Vector | AV:N/AC:M/Au:N/C:P/I:N/A:N |
Name of the Vulnerable Software and Affected Versions
Sielco Sistemi Winlog Pro SCADA versions prior to 2.07.17
Sielco Sistemi Winlog Lite SCADA versions prior to 2.07.17
Description
The issue allows remote attackers to read arbitrary files via port 46824 TCP packets. This is achieved by specifying a file-open operation with opcode
0x78 and a .. (dot dot) in a pathname, followed by a file-read operation with opcode 0x96, 0x97, or 0x98.Recommendations
For Sielco Sistemi Winlog Pro SCADA versions prior to 2.07.17, update to version 2.07.17 or later.
For Sielco Sistemi Winlog Lite SCADA versions prior to 2.07.17, update to version 2.07.17 or later.
Exploit
Fix
Path traversal
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Winlog Lite Scada
Winlog Pro Scada