PT-2014-1178 · Siemens · Simatic S7-1200 Cpu
Published
2014-03-20
·
Updated
2020-02-10
·
CVE-2014-2254
CVSS v2.0
7.8
High
| Vector | AV:N/AC:L/Au:N/C:N/I:N/A:C |
Name of the Vulnerable Software and Affected Versions
Siemens SIMATIC S7-1200 CPU PLC devices with firmware prior to 4.0
Description
The issue allows a remote attacker to cause a denial of service, resulting in the device entering defect mode, by sending crafted HTTP packets to the TCP port 80. This can lead to the device requiring a "cold" restart.
Recommendations
For Siemens SIMATIC S7-1200 CPU PLC devices with firmware prior to 4.0, update the firmware to version 4.0 or later to resolve the issue. As a temporary workaround, consider restricting access to the TCP port 80 to minimize the risk of exploitation.
Fix
Improper Resource Release
Found an issue in the description? Have something to add? Feel free to write us 👾
Related Identifiers
Affected Products
Simatic S7-1200 Cpu