PT-2016-2995 · Siemens · Sicam Pas
Published
2016-12-05
·
Updated
2023-10-17
·
CVE-2016-9157
CVSS v3.1
9.8
Critical
| Vector | AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
Name of the Vulnerable Software and Affected Versions
Siemens SICAM PAS versions prior to V8.09
Description
The issue is related to inadequate access control in the SICAM PAS telecontrol system, which could allow a remote attacker to cause a Denial of Service condition and potentially lead to unauthenticated remote code execution. This can be achieved by sending specially crafted packets to port 19234/TCP.
Recommendations
For versions prior to V8.09, update to version V8.09 or later to resolve the issue. As a temporary workaround, consider restricting access to port 19234/TCP to minimize the risk of exploitation.
Fix
Improper Access Control
RCE
Found an issue in the description? Have something to add? Feel free to write us 👾
Related Identifiers
Affected Products
Sicam Pas