PT-2017-19300 · Siemens · Simatic Logon
Published
2017-08-08
·
Updated
2017-11-22
·
CVE-2017-9938
CVSS v3.1
7.5
High
| Vector | AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
Name of the Vulnerable Software and Affected Versions
Siemens SIMATIC Logon versions prior to V1.6
Description
A vulnerability was discovered that could allow specially crafted packets sent to the SIMATIC Logon Remote Access service on port 16389/tcp to cause a Denial-of-Service condition. The service restarts automatically.
Recommendations
For versions prior to V1.6, update to version V1.6 or later to resolve the issue. As a temporary workaround, consider restricting access to the SIMATIC Logon Remote Access service on port 16389/tcp to minimize the risk of exploitation.
Fix
RCE
Memory Corruption
Found an issue in the description? Have something to add? Feel free to write us 👾
Related Identifiers
Affected Products
Simatic Logon