PT-2017-19300 · Siemens · Simatic Logon

Published

2017-08-08

·

Updated

2017-11-22

·

CVE-2017-9938

CVSS v3.1

7.5

High

VectorAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Name of the Vulnerable Software and Affected Versions Siemens SIMATIC Logon versions prior to V1.6
Description A vulnerability was discovered that could allow specially crafted packets sent to the SIMATIC Logon Remote Access service on port 16389/tcp to cause a Denial-of-Service condition. The service restarts automatically.
Recommendations For versions prior to V1.6, update to version V1.6 or later to resolve the issue. As a temporary workaround, consider restricting access to the SIMATIC Logon Remote Access service on port 16389/tcp to minimize the risk of exploitation.

Fix

RCE

Memory Corruption

Found an issue in the description? Have something to add? Feel free to write us 👾

Weakness Enumeration

Related Identifiers

CVE-2017-9938

Affected Products

Simatic Logon