PT-2018-18260 · Schneider Electric · Micom Px4X+2
Published
2018-04-18
·
Updated
2018-05-29
·
CVE-2018-7758
CVSS v2.0
3.3
Low
| Vector | AV:A/AC:L/Au:N/C:N/I:N/A:P |
Name of the Vulnerable Software and Affected Versions:
Schneider Electric's MiCOM Px4x (P540 range excluded) with legacy Ethernet board
Schneider Electric's MiCOM P540D Range with Legacy Ethernet Board
Schneider Electric's MiCOM Px4x Rejuvenated
Description:
A denial of service issue exists due to TCP/IP open requests on port 20000 (DNP3oE) when an older TCI/IP session is still open with an identical IP address and port number, potentially causing loss of network communication.
Recommendations:
For Schneider Electric's MiCOM Px4x (P540 range excluded) with legacy Ethernet board, consider restricting access to port 20000 to minimize the risk of exploitation.
For Schneider Electric's MiCOM P540D Range with Legacy Ethernet Board, avoid using identical IP address and port number for new TCP/IP sessions if an older session is still open.
For Schneider Electric's MiCOM Px4x Rejuvenated, restrict network communication on port 20000 until a fix is available.
Fix
Insufficient Session Expiration
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Micom P540D Range
Micom Px4X
Micom Px4X Rejuvenated