PT-2018-2165 · Siemens · Simatic S7-1200+1
Published
2018-11-13
·
Updated
2019-10-09
·
CVE-2018-13815
CVSS v3.1
7.5
High
| Vector | AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
Name of the Vulnerable Software and Affected Versions
SIMATIC S7-1200 versions all
SIMATIC S7-1500 versions prior to V2.6
Description
A vulnerability has been identified that could allow an attacker to exhaust the available connection pool of an affected device by opening a sufficient number of connections to it. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit this issue. If exploited, it could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication, no public exploitation of this issue was known.
Recommendations
For SIMATIC S7-1200, restrict access to port 102/tcp to minimize the risk of exploitation.
For SIMATIC S7-1500 versions prior to V2.6, consider upgrading to version V2.6 or later to resolve the issue.
As a temporary workaround, consider limiting the number of connections to the device to prevent exhaustion of the available connection pool.
Fix
Resource Exhaustion
Found an issue in the description? Have something to add? Feel free to write us 👾
Related Identifiers
Affected Products
Simatic S7-1200
Simatic S7-1500