PT-2018-2165 · Siemens · Simatic S7-1200+1

Published

2018-11-13

·

Updated

2019-10-09

·

CVE-2018-13815

CVSS v3.1

7.5

High

VectorAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Name of the Vulnerable Software and Affected Versions SIMATIC S7-1200 versions all SIMATIC S7-1500 versions prior to V2.6
Description A vulnerability has been identified that could allow an attacker to exhaust the available connection pool of an affected device by opening a sufficient number of connections to it. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit this issue. If exploited, it could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication, no public exploitation of this issue was known.
Recommendations For SIMATIC S7-1200, restrict access to port 102/tcp to minimize the risk of exploitation. For SIMATIC S7-1500 versions prior to V2.6, consider upgrading to version V2.6 or later to resolve the issue. As a temporary workaround, consider limiting the number of connections to the device to prevent exhaustion of the available connection pool.

Fix

Resource Exhaustion

Found an issue in the description? Have something to add? Feel free to write us 👾

Weakness Enumeration

Related Identifiers

BDU:2019-00118
CVE-2018-13815

Affected Products

Simatic S7-1200
Simatic S7-1500