PT-2019-4788 · Siemens · Simatic S7-300
Published
2019-01-08
·
Updated
2019-10-03
·
CVE-2018-16561
CVSS v2.0
7.8
High
| Vector | AV:N/AC:L/Au:N/C:N/I:N/A:C |
Name of the Vulnerable Software and Affected Versions
SIMATIC S7-300 CPUs versions prior to V3.X.16
Description
A vulnerability has been identified that improperly validates S7 communication packets, potentially causing a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to send a specially crafted S7 communication packet to a communication interface of the CPU, including Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security issue. This could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system.
Recommendations
For versions prior to V3.X.16, update to a version V3.X.16 or later to resolve the security issue. As a temporary workaround, consider restricting access to the communication interfaces, including Ethernet, PROFIBUS, and Multi Point Interfaces (MPI), to minimize the risk of exploitation.
Fix
RCE
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Simatic S7-300