PT-2019-9692 · Abb · Pluto Safety Plc Gateway Ethernet+2
Published
2019-01-03
·
Updated
2019-10-09
·
CVE-2018-18995
CVSS v2.0
7.5
High
| Vector | AV:N/AC:L/Au:N/C:P/I:P/A:P |
Name of the Vulnerable Software and Affected Versions
Pluto Safety PLC Gateway Ethernet devices ABB GATE-E1 and GATE-E2 all versions
Description
The issue concerns the lack of authentication configuration on administrative telnet or web interfaces, which could enable various attack vectors. This includes conducting device resets, reading or modifying registers, and changing configuration settings such as IP addresses.
Recommendations
For Pluto Safety PLC Gateway Ethernet devices ABB GATE-E1 and GATE-E2, consider restricting access to the administrative telnet and web interfaces until a fix is available. As a temporary workaround, limit network exposure and implement additional security measures to minimize the risk of exploitation. At the moment, there is no information about a newer version that contains a fix for this vulnerability.
Missing Authentication
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Gate-E1
Gate-E2
Pluto Safety Plc Gateway Ethernet