PT-2020-16029 · Siemens · Logo! 8 Bm
Published
2020-12-14
·
Updated
2020-12-16
·
CVE-2020-25232
CVSS v3.1
7.5
High
| Vector | AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N |
Name of the Vulnerable Software and Affected Versions
LOGO! 8 BM (incl. SIPLUS variants) versions prior to V8.3
Description
A security issue has been identified due to the use of an insecure random number generation function and a deprecated cryptographic function. This could allow an attacker to extract the key used for communication with an affected device on port 8080/tcp.
Recommendations
For versions prior to V8.3, update to version V8.3 or later to resolve the issue. As a temporary workaround, consider restricting access to port 8080/tcp to minimize the risk of exploitation.
Fix
Use of a Broken Cryptographic Algorithm
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Logo! 8 Bm