PT-2020-5521 · Rockwell Automation · Factorytalk Linx
Published
2020-12-29
·
Updated
2020-12-30
·
CVE-2020-5801
CVSS v2.0
7.8
High
| Vector | AV:N/AC:L/Au:N/C:N/I:N/A:C |
Name of the Vulnerable Software and Affected Versions
FactoryTalk Linx (affected versions not specified)
Description
The issue is related to the CFTLDManager::HandleRequest function in RnaDaSvr.dll, which can be triggered by an attacker sending an OpenNamespace message to port 4241 with a valid session-id. This results in an unhandled exception, causing process termination. The problem is associated with inadequate handling of exceptional states.
Recommendations
At the moment, there is no information about a newer version that contains a fix for this vulnerability.
Improper Handling of Exceptional Conditions
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Factorytalk Linx