PT-2021-22107 · Delta Electronics · Diaenergie
Michael Heinzl
·
Published
2021-08-30
·
Updated
2021-09-07
·
CVE-2021-38393
CVSS v2.0
10
Critical
| Vector | AV:N/AC:L/Au:N/C:C/I:C/A:C |
Name of the Vulnerable Software and Affected Versions
Delta Electronics DIAEnergie versions 1.7.5 and prior
Description
A Blind SQL injection issue exists in the "/DataHandler/HandlerAlarmGroup.ashx" endpoint. The application does not properly validate the user-controlled value supplied through the
agid parameter before using it as part of an SQL query. A remote, unauthenticated attacker can exploit this issue to execute arbitrary code in the context of NT SERVICEMSSQLSERVER.Recommendations
For versions 1.7.5 and prior, consider disabling access to the "/DataHandler/HandlerAlarmGroup.ashx" endpoint until a patch is available. Restrict input for the
agid parameter to prevent malicious SQL queries. At the moment, there is no information about a newer version that contains a fix for this vulnerability.SQL injection
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Diaenergie