PT-2022-10176 · Automationdirect · Automation Direct Click Plc Cpu Modules
Adeen Ayub
+2
·
Published
2022-04-04
·
Updated
2022-04-13
·
CVE-2021-32984
CVSS v3.1
9.8
Critical
| Vector | AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
Name of the Vulnerable Software and Affected Versions
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs versions prior to v3.00
Description
The issue allows an attacker to connect to the PLC and read the project without authorization during the time it is unlocked by an authorized user, resulting in a privilege escalation. This occurs because all programming connections receive the same unlocked privileges.
Recommendations
For Automation Direct CLICK PLC CPU Modules: C0-1x CPUs versions prior to v3.00, update the firmware to version v3.00 or later to resolve the issue. As a temporary workaround, consider restricting access to the PLC when it is unlocked by an authorized user to minimize the risk of exploitation.
Fix
Improper Authentication
Authentication Bypass Using an Alternate Path or Channel
Found an issue in the description? Have something to add? Feel free to write us 👾