PT-2023-29311 · Johnson Controls · Facility Explorer+1
Published
2023-12-07
·
Updated
2023-12-19
·
CVE-2023-4486
CVSS v3.1
7.5
High
| Vector | AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
Name of the Vulnerable Software and Affected Versions
Johnson Controls Metasys NAE55, SNE, and SNC engines versions prior to 11.0.6 and 12.0.4
Facility Explorer F4-SNC engines versions prior to 11.0.6 and 12.0.4
Description
Under certain circumstances, invalid authentication credentials could be sent to the "login endpoint" of the affected engines to cause denial-of-service.
Recommendations
For Johnson Controls Metasys NAE55, SNE, and SNC engines versions prior to 11.0.6 and 12.0.4, update to version 11.0.6 or 12.0.4 or later.
For Facility Explorer F4-SNC engines versions prior to 11.0.6 and 12.0.4, update to version 11.0.6 or 12.0.4 or later.
As a temporary workaround, consider restricting access to the "login endpoint" until a patch is available.
Fix
Resource Exhaustion
Allocation of Resources Without Limits
Found an issue in the description? Have something to add? Feel free to write us 👾
Related Identifiers
Affected Products
Facility Explorer
Metasys