PT-2023-4361 · Triangle Microworks · Triangle Microworks Scada Data Gateway
Published
2023-08-04
·
Updated
2024-05-05
·
CVE-2023-39464
CVSS v2.0
8.3
High
| Vector | AV:N/AC:L/Au:M/C:C/I:C/A:C |
Name of the Vulnerable Software and Affected Versions
Triangle MicroWorks SCADA Data Gateway (affected versions not specified)
Description
This issue allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this issue, the existing authentication mechanism can be bypassed. The specific flaw exists within the configuration of the GTWWebMonitorService service, where the path to the service executable contains spaces not surrounded by quotations, allowing an attacker to leverage this flaw to execute arbitrary code in the context of root.
Recommendations
At the moment, there is no information about a newer version that contains a fix for this issue.
Fix
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Triangle Microworks Scada Data Gateway