PT-2025-12793 · Rtu500 · Rtu500
Published
2025-03-25
·
Updated
2025-03-25
·
CVE-2024-10037
CVSS v3.1
4.4
Medium
| Vector | AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:N/A:H |
Name of the Vulnerable Software and Affected Versions
RTU500 versions prior to 13.7.0
Description
A vulnerability exists in the RTU500 web server component that can cause a denial of service to the RTU500 CMU application if a specially crafted message sequence is executed on a WebSocket connection. An attacker must be properly authenticated and the test mode function of RTU500 must be enabled to exploit this vulnerability. The affected CMU will automatically recover itself if an attacker successfully exploits this vulnerability.
Recommendations
For versions prior to 13.7.0, update to version 13.7.0 or later to resolve the issue. As a temporary workaround, consider disabling the test mode function of RTU500 to minimize the risk of exploitation. Restrict access to authenticated users and limit the use of WebSocket connections to necessary applications only.
Fix
DoS
NULL Pointer Dereference
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Rtu500