PT-2025-6206 · Siemens · Siplus S7-1200 Cpu+1

Gao Jian

·

Published

2025-02-11

·

Updated

2025-02-11

·

CVE-2025-24812

CVSS v2.0

6.8

Medium

VectorAV:N/AC:L/Au:S/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions: SIMATIC S7-1200 CPU versions prior to V4.7 SIPLUS S7-1200 CPU versions prior to V4.7
Description: A vulnerability has been identified in the affected devices, where they do not process correctly certain specially crafted packets sent to port 102/tcp. This could allow an attacker to cause a denial of service in the device.
Recommendations: For SIMATIC S7-1200 CPU versions prior to V4.7, update to version V4.7 or later to resolve the issue. For SIPLUS S7-1200 CPU versions prior to V4.7, update to version V4.7 or later to resolve the issue. As a temporary workaround, consider restricting access to port 102/tcp to minimize the risk of exploitation.

Fix

Weakness Enumeration

Related Identifiers

BDU:2026-00194
CVE-2025-24812

Affected Products

Simatic S7-1200 Cpu
Siplus S7-1200 Cpu